GPU1-C20, GPU1-C40, GPU1-C60, GPU1-C80, GPU1-C100 SPD (Surge Protection Device).
Feature:
1. Voltage Limiting Type SPD.
2. Degradation Indication.
3. Remote Communication.
4. New Thermal Trip Technology.
Model | GPU1-C20 | GPU1-C40 | GPU1-C60 | GPU1-C80 | GPU1-C100 | |
Max. Continuous Operating Voltage Uc (V) | 385/460 | 385/460 | 385/460 | 385/460 | 385/460 | |
Nominal Discharging Current In (8/20us) (KA) | 10 | 20 | 30 | 40 | 50 | |
Max. Discharging Current Imax (8/20us) (KA) | 20 | 40 | 60 | 80 | 100 | |
Protection Level Up (KV) | L/N-PE | 1.2 | 1.6/1.8 | 2.0/2.2 | 2.2/2.5 | 2.5/3.0 |
N-PE | 1.0 | 1.2 | 1.5 | 2.0 | 2.5 | |
Back-up Protector (SCB) | GP-BP/20 | GP-BP/40 | GP-BP/60 | GP-BP/80 | GP-BP/100 | |
Protection Grade | IP20 | |||||
OPerating Temperature | -40 centigrade to +70 centigrade | |||||
Wiring Capacity | 6 to 25 square mm | |||||
Flame Retardant Grade | UL94V-0 | |||||
Relative Humidity | Less Than 95% | |||||
Combination Mode | 1P/2P/3P/4P | |||||
1P+N/3P+N | ||||||
Remote Signal Contact | Optional | |||||
Switching Contact |