Electricity Type: | AC |
---|---|
Number of Pole: | 3 |
Phase: | 3 |
Still deciding? Get samples of US$ 20/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
GSN1 series of reversing contactors are used for controlling reversible motor and dual power supply.
Model | GSN1-09 | GSN1-12 | GSN1-18 | GSN1-25 | GSN1-32 | GSN1-38 | GSN1-40 | GSN1-50 | GSN1-65 | GSN1-80 | GSN1-95 | GSN1-115 | GSN1-150 | ||
Electrical parameters | |||||||||||||||
Rated Insulation voltage Ui (V) | 690 | 1000 | |||||||||||||
Rated voltage Ue (V) | 380/660 | ||||||||||||||
Rated current Ie (A) | AC-1 | 25 | 25 | 32 | 40 | 50 | 50 | 60 | 80 | 80 | 125 | 125 | 200 | 200 | |
AC-3 | 380V | 9 | 12 | 18 | 25 | 32 | 38 | 40 | 50 | 65 | 80 | 85 | 115 | 150 | |
660V | 6.6 | 8.9 | 12 | 18 | 21 | 21.5 | 34 | 39 | 42 | 49 | 49 | 86 | 107 | ||
AC-4 | 380V | 3.5 | 5 | 7.7 | 8.5 | 12 | 13.9 | 18.5 | 24 | 28 | 37 | 44 | 52 | 60 | |
660V | 1.5 | 2 | 3.8 | 4.4 | 7.5 | 8 | 9 | 12 | 14 | 17.3 | 21.3 | 25 | 38 | ||
AC-3 | Electric life (10000 times) | >200 | >200 | >150 | >150 | >150 | >100 | >150 | >150 | >150 | >150 | >100 | >80 | >80 | |
Operation frequency per hour | 1200 | 1200 | 1200 | 1200 | 1000 | 1000 | 1000 | 1000 | 1000 | 750 | 750 | 750 | 750 | ||
AC-4 | Electric life (10000 times) | >20 | >20 | >20 | >20 | >20 | >15 | >15 | 15 | 15 | >10 | >10 | >10 | >10 | |
Operation frequency per hour | 300 | 150 | |||||||||||||
Mechanical life (10000 times) | 300 | ||||||||||||||
Main contact and Auxiliary contact | 2*(3P+1NO) or 2*(3P+1NC) | 2*(3P+1NO+1NC) | 2*(3P) | ||||||||||||
Auxiliary contact | |||||||||||||||
Rated voltage Ue (V) | 380Vac/220Vdc | ||||||||||||||
Conventional thermal current Ith (A) | 10 | ||||||||||||||
Rated current Ie (A) | AC-15(360VA) | 0.95 | |||||||||||||
DC-13(33W) | 0.15 | ||||||||||||||
Min. load | 24V 10mA | ||||||||||||||
Coil parameters | |||||||||||||||
Coil voltage Us (V) | 24V 50Hz/60Hz, 48V 50Hz/60Hz, 110V 50Hz/60Hz, 220V 50Hz/60Hz, 380V 50Hz/60Hz, | ||||||||||||||
Pull-in voltage (V) | 0.85-1.10Us | ||||||||||||||
Drop-out voltage (V) | 0.20-0.75Us | ||||||||||||||
Pull-in power (VA) | 76 | 76 | 76 | 110 | 110 | 110 | 230 | 230 | 230 | 230 | 230 | 300 | 300 | ||
Hold power (VA) | 10 | 10 | 10 | 11 | 11 | 11 | 32 | 32 | 32 | 32 | 32 | 28 | 28 | ||
Pull-in time (ms) | 12 to 30 | 15 to 40 | 20 to 40 | 20 to 50 | |||||||||||
Drop-out time (ms) | 10 to 25 | 5 to 30 | 6 to 30 | 6 to 30 | |||||||||||
Standard | IEC60947-4-1, EN60947-4-1 | ||||||||||||||
Net weight (KG) | 0.75 | 0.8 | 1.15 | 1.2 | 1.35 | 1.35 | 2.7 | 2.75 | 2.8 | 3.3 | 3.4 | 6.05 | 6.25 |