GSM3 series of molded case circuit breaker is used in the circuit of 50Hz or 60Hz, with rated insulation voltage of 1000Vdc, with rated voltage up to 690Vac, with rated current from 10A to 800A for the purpose of infrequently switching the circuit and starting a motor. The circuit breaker has short circuit protection and overload protection, and also has isolating function. Under-voltage release, shunt release, alarming contact, auxiliary contact, motor-operated mechanism are options.
Frame Current Inm (A) | 63 | 125 | |||||||||||||
Model | GSM3-63 | GSM3-63L | GSM3-63M | GSM3-125 | GSM3-125N | GSM3-125L | GSM3-125M | GSM3-125H | |||||||
Rated current In(A) | 10, 16, 20, 25, 32, 40, 50, 63 | 10, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125 | |||||||||||||
Pole number | 2P | 3P | 4P | 3P | 4P | 2P | 3P | 3P | 4P | 3P | 4P | 3P | 4P | ||
Rated insulation voltage (V) | 800 | 1000 | |||||||||||||
Rated voltage(V) | AC400V DC250V | AC400V | AC400V DC250V | AC400V | AC400V | AC400V AC550V AC690V | AC400V | ||||||||
Rated impulse withstand voltage Uimp (V) | 8000 | 8000 | |||||||||||||
Flashover distance (mm) | 0 | 50 | |||||||||||||
Ultimate short circuit breaking capacity Icu (KA) | AC400V | 50 | 40 | 50 | 50 | 35 | 50 | 75 | 100 | ||||||
AC550V | / | / | / | / | / | / | 40 | / | |||||||
AC690V | / | / | / | / | / | / | 20 | / | |||||||
DC250V | 20 | / | / | 20 | / | / | / | / | |||||||
Rated service short circuit breaking capacity Ics (KA) | AC400V | 40 | 40 | 40 | 40 | 22 | 40 | 55 | 70 | ||||||
AC550V | / | / | / | / | / | / | 40 | / | |||||||
AC690V | / | / | / | / | / | / | 10 | / | |||||||
DC250V | 15 | / | / | 15 | / | / | / | / | |||||||
Electrical life (times) | 8000 | 8000 (AC400V), 1500 (AC690V) | |||||||||||||
Mechanical life (times) | Maintainance-free | 20000 | 20000 | ||||||||||||
With maintainance | 40000 | 40000 | |||||||||||||
Outline dimension (mm) | W | 61 | 78 | 103 | 78 | 103 | 65 | 92 | 92 | 122 | 92 | 122 | 92 | 122 | |
L | 135 | 150 | |||||||||||||
H | 74 | 82 | |||||||||||||
Net weight (KG) | 0.8 | 1 | 1.4 | 1 | 1.4 | 1 | 1.2 | 1.5 | 2 | 1.5 | 2 | 1.5 | 2 | ||
Standard | IEC60947-2/EN60947-2 |
Frame Current Inm (A) | 160 | 250 | ||||||||||||||
Model | GSM3E-160L | GSM3E-160M | GSM3E-160H | GSM3-250 | GSM3-250N | GSM3-250L | GSM3-250M | GSM3-250H | ||||||||
Rated current In(A) | 100 , 125, 140, 160 | 100 , 125, 140, 160, 180, 200, 225, 250 | ||||||||||||||
Pole number | 3P | 4P | 3P | 4P | 3P | 4P | 2P | 3P | 3P | 4P | 3P | 4P | 3P | 4P | ||
Rated insulation voltage (V) | 1000 | 1000 | ||||||||||||||
Rated voltage(V) | AC400V | AC400V AC690V | AC400V | AC400 DC250 | AC400 | AC400V | AC400V AC550V AC690V | AC400V | ||||||||
Rated impulse withstand voltage Uimp (V) | 8000 | 8000 | ||||||||||||||
Flashover distance (mm) | 50 | 50 | ||||||||||||||
Ultimate short circuit breaking capacity Icu (KA) | AC400V | 50 | 75 | 100 | 50 | 35 | 50 | 75 | 100 | |||||||
AC550V | / | / | / | / | / | / | 40 | / | ||||||||
AC690V | / | 20 | / | / | / | / | 20 | / | ||||||||
DC250V | / | / | / | 20 | / | / | / | / | ||||||||
Rated service short circuit breaking capacity Ics (KA) | AC400V | 40 | 55 | 70 | 40 | 25 | 40 | 55 | 70 | |||||||
AC550V | / | / | / | / | / | / | 40 | / | ||||||||
AC690V | / | 10 | / | / | / | / | 10 | / | ||||||||
DC250V | / | / | / | 15 | / | / | / | / | ||||||||
Electrical life (times) | 8000(AC400V), 1000 (AC690) | 8000(AC400V), 1500 (AC690) | ||||||||||||||
Mechanical life (times) | Maintainance-free | 20000 | 20000 | |||||||||||||
With maintainance | 40000 | 40000 | ||||||||||||||
Outline dimension (mm) | W | 107 | 142 | 107 | 142 | 107 | 142 | 75 | 107 | 107 | 142 | 107 | 142 | 107 | 142 | |
H | 165 | 165 | ||||||||||||||
D | 85 | 85 | ||||||||||||||
Net weight (KG) | 2.3 | 3 | 2.3 | 3 | 2.3 | 3 | 1.6 | 2 | 2.3 | 3 | 2.3 | 3 | 2.3 | 3 | ||
Standard | IEC60947-2/EN60947-2 |
Frame Current Inm (A) | 400 | 630 | 800 | |||||||||||||||||||
Model | GSM3-400N | GSM3-400L | GSM3-400M | GSM3-400H | GSM3-630N | GSM3-630L | GSM3-630M | GSM3-630H | GSM3-800L | GSM3-800M | GSM3-800H | |||||||||||
Rated current In(A) | 225, 250, 315, 350, 400 | 400, 500, 630 | 630, 700, 800 | |||||||||||||||||||
Pole number | 3P | 3P | 4P | 3P | 4P | 3P | 4P | 3P | 3P | 4P | 3P | 4P | 3P | 4P | 3P | 4P | 3P | 4P | 3P | 4P | ||
Rated insulation voltage (V) | 1000 | 1000 | 1000 | |||||||||||||||||||
Rated voltage(V) | AC400V | AC400V | AC400V AC550V AC690V | AC400V | AC400V | AC400V | AC400V AC550V AC690V | AC400V | AC400V | AC400V AC550V AC690V | AC400V | |||||||||||
Rated impulse withstand voltage Uimp (V) | 8000 | 8000 | 8000 | |||||||||||||||||||
Flashover distance (mm) | 100 | 100 | 100 | |||||||||||||||||||
Ultimate short circuit breaking capacity Icu (KA) | AC400V | 35 | 55 | 75 | 100 | 35 | 55 | 75 | 100 | 55 | 75 | 100 | ||||||||||
AC550V | / | / | 50 | / | / | / | 50 | / | / | 55 | / | |||||||||||
AC690V | / | / | 20 | / | / | / | 20 | / | / | 35 | / | |||||||||||
DC250V | / | / | / | / | / | / | / | / | / | / | / | |||||||||||
Rated service short circuit breaking capacity Ics (KA) | AC400V | 35 | 55 | 75 | 80 | 35 | 55 | 75 | 80 | 55 | 75 | 80 | ||||||||||
AC550V | / | / | 50 | / | / | / | 50 | / | / | 55 | / | |||||||||||
AC690V | / | / | 15 | / | / | / | 15 | / | / | 25 | / | |||||||||||
DC250V | / | / | / | / | / | / | / | / | / | / | / | |||||||||||
Electrical life (times) | 7500 (AC400V), 1000 (AC690V) | 7500 (AC400V), 1000 (AC690V) | 7500 (AC400V), 1000 (AC690V) | |||||||||||||||||||
Mechanical life (times) | Maintainance-free | 10000 | 10000 | 10000 | ||||||||||||||||||
With maintainance | 20000 | 20000 | 20000 | |||||||||||||||||||
Outline dimension (mm) | W | 150 | 150 | 198 | 150 | 198 | 150 | 198 | 182 | 182 | 240 | 182 | 240 | 182 | 240 | 210 | 280 | 210 | 280 | 210 | 280 | |
H | 257 | 270 | 280 | |||||||||||||||||||
D | 98.5 | 103 | 103 | |||||||||||||||||||
Net weight (KG) | 5 | 5 | 6.4 | 5 | 6.4 | 5 | 6.4 | 6.8 | 6.8 | 8.5 | 6.8 | 8.5 | 6.8 | 8.5 | 8 | 10.5 | 8 | 10.5 | 8 | 10.5 | ||
Standard | IEC60947-2/EN60947-2 |