Electricity Type: | AC |
---|---|
Number of Pole: | 2, 3, 4, 5 |
Phase: | 2, 3, 4, 5 |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
CJ156 series of magnetic contactor (New generation of CJ12 and CJ24) is used in the circuit of 50Hz or 60Hz with rated voltage up to 660Vac, and with rated current from 100A to 630A for AC3 usage category, or with rated voltage up to 1000Vac, and with rated current from 800A to 1800A for AC3 usage category, for the purpose of frequently closing or breaking circuit remotely, and starting, stopping or anti-phase running or reverse braking motor. The contactor complies with IEC60947-4-1 and IEC60947-5-1 standard.
Model | Rated insulation voltage Ui (V) |
Rated Voltage Ue (V) |
Conventional thermal current Ith (A) | Rated current Ie (A) | ||||
Intermittent periodic duty | Uninterrupted duty | |||||||
AC-1, AC-2, AC-3 | AC-4 | |||||||
380V | 660V | 380V | 660V | |||||
CJ156-100 | 660V | 380V or 660V | 100A | 100A | 63A | 100A | 40A | 100A |
CJ156-160 | 160A | 160A | 80A | 160A | 63A | 160A | ||
CJ156-250 | 250A | 250A | 160A | 250A | 100A | 250A | ||
CJ156-400 | 400A | 400A | 250A | 400A | 160A | 400A | ||
CJ156-630 | 630A | 630A | 400A | 630A | 250A | 630A |
Model | Rated current at 380V/ 400V for AC-3 (Ie) | Controlled motor power for AC-3 application | Power pole number | |
380/400V | 660V | 2P 3P 4P 5P |
||
CJ156-100 | 100A | 50KW | 75KW | |
CJ156-160 | 160A | 75KW | 100KW | |
CJ156-250 | 250A | 129KW | 147KW | |
CJ156-400 | 400A | 200KW | 280KW | |
CJ156-630 | 630A | 335KW | 450KW |
Model | Rated voltage Ie (V) | Electrical life | Mechanical life | ||||||
Closing or Breaking condition | Power on time | Operation frequency per hour | Electrical life | ||||||
I/Ie | U/Ue | CosФ±0.05 | For 2, 3 pole | For 4, 5 pole | |||||
CJ156-100 CJ156-160 CJ156-250 |
380V or 660V |
2.5 |
1 |
0.65 |
0.2s |
600 cycles per hour | 300000 cycles | 6000000 cycles | 600000 cycles |
CJ156-400 CJ156-630 |
300 cycles per hour | 240000 cycles | 3000000 cycles | 300000 cycles |
Model | FC1-60 | FC1-51 | FC1-42 | FC1-33 | FC1-24 | FC1-15 | FC1-06 |
NO contact quantity | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
NC contact quantity | 0 | 1 | 2 | 3 | 4 | 5 | 6 |
Application | Rated insulation voltage Ui (V) | Rated voltage (Ue) | Conventional thermal current Ith (V) | Rated current (Ie) | Controlled capacity | Auxiliary contact |
AC-15 | 380V | Up to 380V | 10A | 0.95 | 360VA | 1NC |
DC-13 | Up to 220V | 0.31 | 69W | 1NO |
Model | Rated insulation voltage Ui (V) | Rated voltage Ue (V) | Conventional thermal current Ith (A) | Rated current Ie (A) | Controlled motor power for AC-3 (KW) | Operation frequency per hour | Mechanical life (times) | Elecrical life (times) | ||||
AC-1 | AC-2, AC-3 | |||||||||||
380V | 660V | 380V | 660V | 380V | 660V | |||||||
CJ156-800 | 1000V | 380V, 660V, 1000V | 800A | 800A | 630A | 800A | 551A | 400KW | 560KW | 120 | 1200000 | 150000 |
CJ156-1000 | 1250A | 1250A | 800A | 1000A | 600A | 500KW | 670KW | |||||
CJ156-1500 | 2000A | 2000A | 1250A | 1500A | 690A | 750KW | 750KW | |||||
CJ156-1800 | 2750A | 2750A | 1500A | 1800A | 880A | 900KW | 900KW |