Type: | Power Source Arrester |
---|---|
Structure: | Protective Gap |
Installation: | Parallel Arrester |
Still deciding? Get samples of US$ 15/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
TYPE 2 AC surge protection device
Feature:
Impulse/maximum dischange current (limp/lmax):30kA,60kA
Varistor voltage limiting technology, low residuol voltage design
Pluggable design and intemal thermal disconnection devices
Operating/foult indication,optional remote signal
Conform to IEC 61643-11,EN 61643-11,GB/T 18802.11
MDAY MODEL | MYH60-275 | MYH60-320 | MYH60-385 | MYH60-440 |
Product Description | Typel+2 Surge Protection Device | |||
AC Operating Voltage [Un] | 230Vac | 230Vac | 230Vac | 230Vac |
Maximum Continuous Operating Voltage [Uc] | 275Vac | 320Vac | 385Vac | 440Vac |
Temporary Overvoltage Test Value TOV-5s[Tolerance] [Ut] | 335Vac | 335Vac | 500Vac | 580Vac |
Temporary Overvoltage Test Value TOV-120min[Disconnection][Ut] | 440Vac | 440Vac | 650Vac | 770Vac |
Nominal Discharge Current [8/20μs] [In] | 30kA | 30kA | 30kA | 30kA |
Maximum Discharge Current[8/20μs] [Imax] | 60kA | 60kA | 60kA | 60kA |
Voltage Protection lever [Up] | ≤1.8kA | ≤2.0kA | ≤2.2kA | ≤2.4kA |
Short-circuit Current Rating [Isccr] | 25kA | |||
Response Time [tA] | ≤25ns | |||
Thermal Disconnection Device | Insertion | |||
Max.Backup Fuse | 100A gG Fuse | |||
MECHANICAL DATA | ||||
Product Size | As photo | |||
Wiring Method | Screw terminal2.5-25mm2 [busbar wiring method can be used] | |||
Normal/Fault Display | Green/Red | |||
Remote Signal | Optional | |||
Maximum Remote Signal Load Voltage/Current | 250V/0.5A(AC)30V/3A(DC) | |||
Maximum Cross-sectional Area Of Remote Signal Connection Line | 1.5mm2 | |||
Installation | 35mm din rail | |||
Operating Temperature Range [Tu] | -40 to +85 D37centigrade | |||
Protection Level | IP20 | |||
Enclosure Moterial | Thermoplastic materials,conform to UL94-VO |
MDAY MODEL | PRODUCT CODE | PROOTECTION MODE | In | Imax TOTAL | VOLTAGE PROTECTION LEVEL(UP) | ||
L→PE | L→N | N→PE | |||||
MYN60-275/1+0 | 9070DD2041001 | L/N→PE | 30kA | 60kA | ≤1.8kA | / | ≤1.8kA |
MYN60-275/2+0 | 9070DD2041002 | L,N→PE | 30kA | 120kA | ≤1.8kA | / | ≤1.8kA |
MYN60-275/3+0 | 9070DD2041003 | L→PE | 30kA | 180kA | ≤1.8kA | / | / |
MYN60-275/4+0 | 9070DD2041004 | L,N→PE | 30kA | 240kA | ≤1.8kA | / | ≤1.8kA |
MYN60-275/1+1 | 9070DD2041005 | L→N.N→PE | 30kA | 60kA | / | ≤1.8kA | ≤1.8kA |
MYN60-275/3+1 | 9070DD2041006 | L→N.N→PE | 30kA | 60kA | / | ≤1.8kA | ≤1.8kA |
MYN60-320/1+0 | 9070DD2041007 | L/N→PE | 30kA | 60kA | ≤2.0kA | / | ≤1.8kA |
MYN60-320/2+0 | 9070DD2041008 | L,N→PE | 30kA | 120kA | ≤2.0kA | / | ≤1.8kA |
MYN60-320/3+0 | 9070DD2041009 | L→PE | 30kA | 180kA | ≤2.0kA | / | / |
MYN60-320/4+0 | 9070DD2041010 | L,N→PE | 30kA | 240kA | ≤2.0kA | / | ≤1.8kA |
MYN60-320/1+1 | 9070DD2041011 | L→N.N→PE | 30kA | 60kA | / | ≤2.0kA | ≤1.8kA |
MYN60-320/3+1 | 9070DD2041012 | L→N.N→PE | 30kA | 60kA | / | ≤2.0kA | ≤1.8kA |
MYN60-385/1+0 | 9070DD2041013 | L/N→PE | 30kA | 60kA | ≤2.2kA | / | ≤1.8kA |
MYN60-385/2+0 | 9070DD2041014 | L,N→PE | 30kA | 120kA | ≤2.2kA | / | ≤1.8kA |
MYN60-385/3+0 | 9070DD2041015 | L→PE | 30kA | 180kA | ≤2.2kA | / | / |
MYN60-385/4+0 | 9070DD2041016 | L,N→PE | 30kA | 240kA | ≤2.2kA | / | ≤1.8kA |
MYN60-385/1+1 | 9070DD2041017 | L→N.N→PE | 30kA | 60kA | / | ≤2.2kA | ≤1.8kA |
MYN60-385/3+1 | 9070DD2041018 | L→N.N→PE | 30kA | 60kA | / | ≤2.2kA | ≤1.8kA |
MYN60-440/1+0 | 9070DD2041019 | L/N→PE | 30kA | 60kA | ≤2.4kA | / | ≤1.8kA |
MYN60-440/2+0 | 9070DD2041020 | L,N→PE | 30kA | 120kA | ≤2.4kA | / | ≤1.8kA |
MYN60-440/3+0 | 9070DD2041021 | L→PE | 30kA | 180kA | ≤2.4kA | / | / |
MYN60-440/4+0 | 9070DD2041022 | L,N→PE | 30kA | 240kA | ≤2.4kA | / | ≤1.8kA |
MYN60-440/1+1 | 9070DD2041023 | L→N.N→PE | 30kA | 60kA | / | ≤2.4kA | ≤1.8kA |
MYN60-440/3+1 | 9070DD2041024 | L→N.N→PE | 30kA | 60kA | / | ≤2.4kA | ≤1.8kA |